CPSN-SSI-4C Thermocouple Module for CONPROSYS Nano Series 4ch
CPSN-SSI-4C Thermocouple Module for CONPROSYS Nano Series 4ch
  • SKU: CPSN-SSI-4C
  • Availability: In Stock Many in stock Out of stock BUILT TO ORDER - SHIPS IN 2 - 6 WEEKS

CPSN-SSI-4C Thermocouple Module for CONPROSYS Nano Series 4ch

$181.10
Shipping calculated at checkout.

    This expansion I/O module adds a thermocouple interface to the CPU unit of the CONPROSYS nano series. Each module offers four channels of differential inputs. 

    Compatible with various types of thermocouple inputs 

    This module is compatible with a wide range of thermocouple input types such as J(IEC60584-1), K(IEC60584-1), E(IEC60584-1), N(IEC60584-1), R(IEC60584-1), S(IEC60584-1), and T(IEC60584-1). 

    Cold junction compensation function 

    As cold junction compensation is integrated in the module, there is no need to install a temperature sensor for cold junction compensation externally, and temperature can be measured simply by connecting a thermocouple. 

    LED indicator for status check 

    You can check the error status of the thermocouple, such as disconnected, not-connected, or sensor circuit trouble, with the LED indicator. 

    Easy installation and removal 

    This module can be installed in and removed from the CPU unit without any tools. 

    Adaptable to a wide temperature range between -20 and +60°C 

    The module operates with temperatures between -20 and + 60°C. It can be installed in various environments. 

    No electrolytic capacitor 

    Without an electrolytic capacitor, which has a limited life, we are creating a product with a long-life cycle. 

    Function specifications

    Model Online Model
    Input type Differential input
    Input channel 4ch
    Resolution 24-bit (1/1024 °C)
    Conversion speed*1 251ms (Measure four thermocouples and one cold junction sensor per channel)
    Buffer memory The latest data only
    Conversion start condition Constant update
    Compatible thermocouple sensor J(IEC 60584-1), K(IEC 60584-1), E(IEC 60584-1), N(IEC 60584-1), R(IEC 60584-1), S(IEC 60584-1), T(IEC 60584-1)
    Conversion tolerance Thermocouple type K, J, E, N, T: Within ± [0.3°C + Measured temperature×0.12% (0°C or higher) or 1% (0°C or lower)
    Thermocouple type R, S: Within ± [1.2°C + Measured temperature×0.12%]
    Cold junction sensor Integrated
    Cold junction tolerance *2*3 Within 3.6°C (Vertical installation (Installation angle 0°))
    Isolation Bus isolation
    Isolation withstand voltage 500VDC
    Connector 2 pieces 3.81mm pitch 10-pin termina
    Applicable wire AWG28 - 16
    LED 4 (Green)
    Electricity consumption 5V 0.15A (Max.)
    3.3V 0.05A (Max.)
    Physical dimensions (mm) 15.6(W)×52.6(D)×84(H) (No projection included)
    Weight 50g
    Notes: *1 It is the conversion time of the measurement value. Communication time is not included.
    *2 It is the measured value under the condition of wind speed of 0-0.5m/s in the thermostatic bath.
    *3 The cold junction tolerance is within 4.6 ° C when the product is installed in the orientation other than vertical installation (Installation angle 0 °). Installation orientation requires software command to change the settings. (Default: vertical installation)

    Installation Environment Requirements

    Model Online Model
    Operating ambient temperature -20 - +60°C (Wall installation at an angle of 0°)
    -20°C to +55°C with a vertical installation at an angle of 90° to the left/right or with a plane installation
    Operating ambient humidity 10 - 90%RH (No condensation)
    Non-operating ambient temperature -20 - +60°C
    Non-operating ambient humidity 10 - 90%RH (No condensation)
    Floating dust particles Not to be excessive
    Corrosive gases None
    Line noise Signal Line /±1kV (IEC61000-4-4 Level 3, EN61000-4-4 Level 3)
    Static electricity resistance Touch /±4kV (IEC61000-4-2 Level 2, EN61000-4-2 Level 2)
    Air /±8kV (IEC61000-4-2 Level 3, EN61000-4-2 Level 3)
    Sweep resistance 10 - 57Hz *4 /semi-amplitude vibration 0.15mm, 57 - 150Hz/2.0G 40minutes each in X, Y, and Z directions (JIS C60068-2-6- compliant, IEC60068-2-6-compliant)
    Shock resistance 15G half-sine shock for 11ms in X, Y, and Z directions (JIS C 60068-2-27 -compliant, IEC 60068-2-27 -compliant)
    Standard VCCI Class A, FCC Class A, CE Marking (EMC Directive Class A, RoHS Directive)
    Notes: *4 With the optional DIN rail fitting power supply: 10 - 55Hz (for details, see the user’s guide of the optional power supply).

    Don’t see exactly what you’re looking for? Contec has you covered!

    We offer a wide range of custom engineering and design services:

    • Branding and Labeling
    • Software Image Deployment and BIOS Modification
    • Regulatory Testing and Certification
    • Modification of Existing Contec Hardware Platform
    • Fully Custom System Engineering Design and Development

    Other services include:

    • Life Cycle Management
    • Inventory Management
    • Fulfillment Logistics

    Contact us today to speak with a specialist.

    Online Form

    Email: eShop@us.contec.com

    Phone: +1 321 728 0172

    Contec Americas Inc. currently offers easy online ordering for customers in the United States. Customers wishing to ship internationally can place an order by contacting us by phone +1 (321) 728-0172 or by email at eShop@us.contec.com to place an order. 

     

    Availability*  Time to Ship
    In Stock Shipped within 1-3 business days.
    Built to Order

    Shipped within approximately 2 to 6 weeks.

    Processing time may vary based on component availability and market conditions. A Contec Americas representative will contact you via email or phone to confirm the lead time of your order within 2 business days after your order is placed.  If you are not satisfied with the lead time provided, we will provide a full refund of your order.

     

    *Product availability is visible on the product page above the product description and below the SKU. First, select the desired quantity and configuration options (if applicable). The product availability field will update based on your selections. 

     

    Image: Product Availability Field Location

     

    Please allow additional days in transit for delivery based on your shipment method. If there will be a significant delay in the shipment of your order, we will contact you via email or telephone.

    Contec Americas Inc. ships to verifiable business addresses within the U.S., U.S. Territories.  We do not ship to P.O. Boxes or APO/FPO addresses.

    Shipping and delivery dates are not guaranteed. Orders can be delayed because of payment, billing, or shipping verification in order to prevent fraudulent credit card transactions. Tracking numbers will be sent to the customer when the order has shipped. Orders are not shipped or delivered on weekends or holidays.  Shipping charges are non-refundable.

    Shipping Damage

    Contec Americas, Inc. is not liable for any products damaged or lost during shipping. If you received your order damaged, please contact the shipment carrier to file a claim.

    Please save all packaging materials and damaged goods before filing a claim.

    Customs, Duties and Taxes

    Contec Americas Inc. is not responsible for any customs and taxes applied to your order. All fees imposed during or after shipping are the responsibility of the customer (tariffs, taxes, etc.).

    Complete Contec Catalog

    The Contec Americas eShop represents a limited selection of our extensive catalog of more than 800 products. We are pleased to offer both domestic and international customers technical consultations, quotes and volume pricing from our U.S. office. For qualified customers, we accept purchase orders and offer net terms.  For more information, or to request a quote for a volume order, please contact us at eShop@us.contec.com or call us at +1 (321) 728-0172. Our complete catalog is available on our global website at www.contec.com.

    Questions

    For questions or comments regarding this policy, please contact us at eShop@us.contec.com.

    BACK TO TOP